Si20-701_B Troubleshooting by Remote Controller
338
3.79
PJ
Error in Capacity Setting
Remote Controller Display
PJ
Applicable Models
RZ(Y)
Method of Error Detection
Checks if the value set in the capacity setting adaptor is
the same as the capacity set in the outdoor unit PCB.
Error Decision Conditions
Error is generated when installed with the capacity
setting adaptor incompatible with the PCB. (Judgement is
made only when the power switch is turned ON.)
Supposed Causes
îš„ Inappropriate capacity setting adaptor
îš„ Defective outdoor unit PCB
Troubleshooting
Is
capacity
setting adaptor
connected to outdoor
unit PCB?
NO
YES
Connect adaptor
appropriate to
the model.
Install correct
adaptor.
Check the combination of
capacity setting adaptor
and outdoor unit PCB.
Incorrect combination of capacity setting adaptor and
outdoor unit PCB.
Capacity setting adaptor is not connected to outdoor
unit PCB.
Correct the
combination if it
is incorrect.
Caution
Be sure to turn off the power switch before
connecting or disconnecting connectors, or parts
may be damaged.

Table of Contents

Other manuals for Daikin FAQ71BVV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71BVV1B and is the answer not in the manual?

Daikin FAQ71BVV1B Specifications

General IconGeneral
BrandDaikin
ModelFAQ71BVV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals