EasyManuals Logo

Daikin FAQ71BVV1B Service Manual

Daikin FAQ71BVV1B
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #330 background imageLoading...
Page #330 background image
Troubleshooting by Remote Controller Si20-701_B
323
3.73
LC
Transmission Error
(between Control PCB and
Inverter PCB)
Remote Controller Display
LC
Applicable Models
RZQ-K/H, RZQ(S)-B/C, RZR-KU/HU
Method of Error Detection
Check whether transmission between control PCB and
inverter PCB is carried out normally.
Error Decision Conditions
When the transmission is not carried out in a specified
period of time or longer
Supposed Causes
îš„ Incorrect transmission wiring between control PCB
and inverter PCB/insufficient contact in wiring
îš„ Defective control PCB and inverter PCB
îš„ External factor (Noise, etc.)
îš„ Defective outdoor unit fan motor
îš„ Defective fan motor connector contact

Table of Contents

Other manuals for Daikin FAQ71BVV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71BVV1B and is the answer not in the manual?

Daikin FAQ71BVV1B Specifications

General IconGeneral
BrandDaikin
ModelFAQ71BVV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals