EasyManuals Logo

Daikin FAQ71BVV1B Service Manual

Daikin FAQ71BVV1B
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #259 background imageLoading...
Page #259 background image
Si20-701_B Troubleshooting by Remote Controller
252
3.52
J7
Liquid Pipe Thermistor
Abnormality
Remote Controller Display
J7
Applicable Models
CMSQ
Method of Error Detection
The error is detected according to the temperature
detected by liquid pipe thermistor.
Error Decision Conditions
When the liquid pipe thermistor is short circuited or open
circuited
Supposed Causes
îš„ Defective liquid pipe thermistor (R6T)
îš„ Defective outdoor unit PCB
îš„ Defective thermistor connection

Table of Contents

Other manuals for Daikin FAQ71BVV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71BVV1B and is the answer not in the manual?

Daikin FAQ71BVV1B Specifications

General IconGeneral
BrandDaikin
ModelFAQ71BVV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals