EasyManuals Logo

Daikin FAQ71BVV1B Service Manual

Daikin FAQ71BVV1B
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #382 background imageLoading...
Page #382 background image
Troubleshooting by Remote Controller Si20-701_B
375
3.92
U4
or
UF
Transmission Error
(Between Indoor Unit and
Outdoor Unit)
Remote Controller Display
U4
or
UF
Applicable Models
R(Y)-FU
Method of Error Detection
Micro-computer checks if transmission between indoor
and outdoor units is normal.
Error Decision Conditions
When transmission is not carried out normally for a
certain amount of time
Supposed Causes
îš„ Wiring indoor-outdoor transmission wire is incorrect.
îš„ Defective indoor unit PCB
îš„ Defective outdoor unit PCB
îš„ External factor (Noise, etc.)

Table of Contents

Other manuals for Daikin FAQ71BVV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71BVV1B and is the answer not in the manual?

Daikin FAQ71BVV1B Specifications

General IconGeneral
BrandDaikin
ModelFAQ71BVV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals