EasyManuals Logo

Daikin FAQ71BVV1B Service Manual

Daikin FAQ71BVV1B
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #180 background imageLoading...
Page #180 background image
Troubleshooting by Remote Controller Si20-701_B
173
3.31
E4
Low Pressure System
Abnormality
Remote Controller Display
E4
Applicable Models
RZQ-C
Method of Error Detection
îš„ Detect errors by the low pressure sensor.
Error Decision Conditions
îš„ When the detection pressure is the following value
Actuating pressure: 0.07MPa
Supposed Causes
îš„ Defective low pressure switch
îš„ Disconnection of the wire harness of the low pressure
switch
îš„ Defective connection of the connector of the low
pressure switch
îš„ The refrigerant piping circuit abnormality
îš„ The stop valve is not opened
îš„ Defective outdoor unit main PCB
îš„ Refrigerant shortage

Table of Contents

Other manuals for Daikin FAQ71BVV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71BVV1B and is the answer not in the manual?

Daikin FAQ71BVV1B Specifications

General IconGeneral
BrandDaikin
ModelFAQ71BVV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals