Troubleshooting by Remote Controller Si20-701_B
181
3.33
E6
Compressor Overcurrent
Remote Controller Display
E6
Applicable Model
R(Y)-LU, RR-M
Method of Error Detection
The input current value is detected with a current sensor.
Error Decision Conditions
When the compressor input current exceeds the
specified input current value.
Refer to “Approximate Input current value” on
following page.
Possible Causes
High pressure increased too high
Voltage drop
Stop valve is not opened
Defective compressor (compressor lock)