EasyManuals Logo

Daikin FAQ71BVV1B Service Manual

Daikin FAQ71BVV1B
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #297 background imageLoading...
Page #297 background image
Si20-701_B Troubleshooting by Remote Controller
290
3.65
L5
Output Overcurrent
Detection
Remote Controller Display
L5
Applicable Models
RZQ-K/H, RZQ(S)-B/C, RZR-KU/HU
Method of Error Detection
The error is detected by converting the current flowing to
power transistor into voltage with CT1 (DC current
sensor).
Error Decision Conditions
When overcurrent has run to power transistor
(Actuated even by instantaneous overcurrent)
Supposed Causes
îš„ Defective compressor coil (disconnection, poor
insulation)
îš„ Compressor startup error (mechanical lock)
îš„ Defective inverter PCB
îš„ Instantaneous fluctuation of power supply voltage
îš„ Defective compressor (if bearing is scratched)
îš„ The stop valve is not opened

Table of Contents

Other manuals for Daikin FAQ71BVV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71BVV1B and is the answer not in the manual?

Daikin FAQ71BVV1B Specifications

General IconGeneral
BrandDaikin
ModelFAQ71BVV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals