EasyManuals Logo

Daikin FAQ71BVV1B Service Manual

Daikin FAQ71BVV1B
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #248 background imageLoading...
Page #248 background image
Troubleshooting by Remote Controller Si20-701_B
241
3.47
J1
Pressure Sensor
Abnormality
Remote Controller Display
J1
Applicable Models
RZQ-K, RZQ(S)-C, RZR-KU/HU
Method of Error Detection
The error is detected by the pressure measured with
pressure sensor
Error Decision Conditions
When the detect pressure becomes following;
• Detected pressure ≤ – 0.05MPa continues 185 sec.
• Detected pressure ≥ 4.4MPa continues 185 sec.
Supposed Causes
îš„ Defective pressure sensor
îš„ Defective outdoor unit PCB
îš„ Incorrect connection of connector

Table of Contents

Other manuals for Daikin FAQ71BVV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71BVV1B and is the answer not in the manual?

Daikin FAQ71BVV1B Specifications

General IconGeneral
BrandDaikin
ModelFAQ71BVV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals