Troubleshooting by Remote Controller Si20-701_B
137
Note:
∗1. In the case of R(Y)71, or 100, make sure the short
circuiting connector is correctly mounted.
∗2. R(Y)71, and 100LU, are provided with a safety device
for errors in the compressor.
If the compressor errors due to closed stop valve or
refrigerant shortage, this safety device may be
actuated.
In this case, the compressor cannot restart and its
terminal section has no continuity until the internal
temperature of the compressor falls and the safety
device is reset. (The temperature will fall in a couple
of 10 minutes to a couple of hours.)