EasyManuals Logo

Daikin FAQ71BVV1B Service Manual

Daikin FAQ71BVV1B
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #178 background imageLoading...
Page #178 background image
Troubleshooting by Remote Controller Si20-701_B
171
Remote Controller Display
E4
Applicable Models
RZQ-H, RZQ(S)-B
Method of Error Detection
The protection device circuit checks continuity in the low
pressure switch.
Error Decision Conditions
When the low pressure switch is activated during
compressor operating.
Operating pressure: 0.12 MPa continuous 5 minutes
Supposed Causes
∗ Compressor is not defective.
îš„ Stop valve is not opened
îš„ Defective connection of low pressure switch connector
îš„ Disconnection in low pressure switch harness
îš„ Defective low pressure switch
îš„ Defective refrigerant system
îš„ Refrigerant shortage
îš„ Defective outdoor unit PCB

Table of Contents

Other manuals for Daikin FAQ71BVV1B

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin FAQ71BVV1B and is the answer not in the manual?

Daikin FAQ71BVV1B Specifications

General IconGeneral
BrandDaikin
ModelFAQ71BVV1B
CategoryAir Conditioner
LanguageEnglish

Related product manuals