Troubleshooting by Remote Controller Si20-701_B
321
Remote Controller Display
LC
Applicable Models
RZQG
Method of Error Detection
Check whether transmission between control and
inverter PCB is carried out normally.
Error Decision Conditions
When the transmission is not carried out in a specified
period of time or longer
Supposed Causes
îš„ Defective outdoor unit fan motor
îš„ Defective fan motor connector contact
îš„ Defective control and inverter PCB
îš„ External factor (Noise, etc.)