SiUS04-924 Troubleshooting
Service Diagnosis 97
4.20 Electrical Box Temperature Rise
Remote
Controller
Display
L3
Method of
Malfunction
Detection
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
compressor off.
Malfunction
Decision
Conditions
With the compressor off, the radiation fin temperature is above 212°F(100°C). (Reset is made when
the temperature drops below 158°F(70°C).)
Supposed
Causes
Fin temperature rise due to defective outdoor unit fan
Fin temperature rise due to short-circuit
Fin thermistor defective
Connector in poor contact
Outdoor unit PCB defective
Foreign matter stuck in the outdoor unit fan
Troubleshooting
Check No.07
Refer to P.109
Check No.09
Refer to P.110
(R9294)
Caution
Be sure to turn off the power switch before connecting or disconnecting
the connector, or parts damage may occur.
YES
NO
Slightly dirty
Malfunctioning
Too dirty
Functioning
NO
YES
WARNING
To cool down the electricals, the
outdoor unit fan gets started when
the radiation fin temperature rises
above 185°F(85°C) and stops
itself when it drops below
Turn off the power and turn it on
again.
Check the radiation fin
temperature.
Check No. 07
Check the installation condition.
Radiation fin
dirty?
Above its stop
level?
Check No. 09
Check the outdoor unit fan or
related.
Error again or
outdoor unit fan activated?
Replace the outdoor unit
PCB.
Replace the outdoor unit
PCB.
Replace the fan motor.
Correct the connectors and
fan motor leads.
Clean up the radiation fin.