SiUS04-924 Other Considerations
Others 183
1. Other Considerations
1.1 Trial Operation from the Remote Controller
1.1.1 Trial Operation and Testing
1. Measure the supply voltage and make sure that it falls in the specified range.
2. Trial operation should be carried out in either cooling or heating mode.
3. Carry out the test operation in accordance with the Operation Manual to ensure that all functions
and parts, such as louver movement, are working properly.
The air conditioner requires a small amount of power in its standby mode. If the system is not to
be used for some time after installation, shut off the circuit breaker to eliminate unnecessary
power consumption.
If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the
original operation mode when the circuit breaker is opened again.
For Heat pump In cooling mode, select the lowest programmable temperature; in heating mode, select the highest
programmable temperature.
Trial operation may be disabled in either mode depending on the room temperature.
After trial operation is complete, set the temperature to a normal level.
(78°F to 82°F (26°C to 28°C) in cooling mode, 68°F to 75°F (20°C to 24°C) in heating mode)
For protection, the system disables restart operation for 3 minutes after it is turned off.
1.1.2 Trial operation from Remote Controller
(1) Press the MODE button and select operation mode.
(2) Press the ON/OFF button to turn on the system.
(3) Press the both of TEMP buttons and the MODE button at the same time.
(4) Press the MODE button twice.
(“T” will appear on the display to indicate that Trial Operation is selected.)
(5) Trial operation terminates in approx. 30 minutes and switches into normal mode. To quit a trial
operation, press the ON/OFF button.