Problem Symptoms and Measures SiUS04-924
68 Service Diagnosis
2. Problem Symptoms and Measures
Symptom Check Item Details of Measure
Reference
Page
None of the units operates. Check the power supply. Check to make sure that the rated voltage is
supplied.
—
Check the type of the indoor units. Check to make sure that the indoor unit type is
compatible with the outdoor unit.
—
Check the outdoor air temperature. Heating operation cannot be used when the
outdoor air temperature is 75.2°F(24°C) or
higher (only for heat pump model), and cooling
operation cannot be used when the outside
temperature is below 10.4°F(12°C).*
—
Diagnosis with remote controller
indication
—72
Check the remote controller
addresses.
Check to make sure that address settings for the
remote controller and indoor unit are correct.
—
Operation sometimes
stops.
Check the power supply. A power failure of 2 to 10 cycles can stop air
conditioner operation. (Operation lamp OFF)
—
Check the outdoor air temperature. Heating operation cannot be used when the
outdoor air temperature is 75.2°F(24°C) or
higher (only for heat pump model), and cooling
operation cannot be used when the outside
temperature is below 10.4°F(12°C).*
—
Diagnosis with remote controller
indication
—72
Equipment operates but
does not cool, or does not
heat (only for heat pump
model).
Check for wiring and piping errors in
the indoor and outdoor units
connection wires and pipes.
Conduct the wiring/piping error check described
on the product diagnosis nameplate.
—
Check for thermistor detection errors. Check to make sure that the main unit’s
thermistor has not dismounted from the pipe
holder.
—
Check for faulty operation of the
electronic expansion valve.
Set the units to cooling operation, and compare
the temperatures of the liquid side connection
pipes of the connection section among rooms to
check the opening and closing operation of the
electronic expansion valves of the individual
units.
—
Diagnosis with remote controller
indication
—72
Diagnosis by service port pressure
and operating current
Check for insufficient gas. 110
Large operating noise and
vibrations
Check the output voltage of the power
transistor.
—111
Check the power transistor. — —
Check the installation condition. Check to make sure that the required spaces for
installation (specified in the Engineering Data
Book, etc.) are provided.
—
* 0°F(17.8°C) with low ambient setting: see Page 42.