Other Considerations SiUS04-924
184 Others
1.2 Jumper Settings
1.2.1 When 2 Units are Installed in 1 Room
When 2 indoor units are installed in 1 room, the 2 wireless remote controllers can be set for
different addresses.
How to set the different addresses
Control PCB of the indoor unit
(1) Remove the front grille (6 screws, 3 front grille fixtures)
(2) Remove the electrical wiring box. (1 screw)
(3) Remove the metal plate electrical wiring cover. (4 tabs)
(4) Cut the address jumper JA on the control PCB.
Wireless remote controller
(1) Slide the front cover and take it off.
(2) Cut the address jumper J4.
1.2.2 Jumper Setting
ADDRESS
J4
EXIST
CUT
1
2
J4
(R9676)
ADDRESS
JA
ADDRESS
JA
EXIST
1
CUT 2
(R9677)
Jumper
(On indoor control PCB)
Function When connected
(factory set)
When cut
JC Power failure
recovery function
Auto restart Unit does not resume operation
after recovering from a power
failure. Timer ON-OFF settings
are cleared.
JB Fan speed setting
when compressor is
OFF on thermostat.
(effective only at
cooling operation)
Fan speed setting ;
Remote controller
setting
Fan rpm is set to “0”
<Fan stop>