SiUS04-924 Main Functions
18 Function and Control
1.6 Thermostat Control
Thermostat control is based on the difference between the room temperature and the set point.
Thermostat OFF Condition
The temperature difference is in zone A.
Thermostat ON Condition
The temperature difference is above zone C after being in zone A.
The system resumes from defrost control in any zones except A.
The operation turns on in any zones except A.
The monitoring time has passed while the temperature difference is in zone B.
(Cooling / Dry : 10 minutes, Heating : 10 seconds)
Cooling / Dry
Heating
B
A
OFF
ON
C
Cooling : –0.9˚F(–0.5˚C)
Dry : –0.9˚F(–0.5˚C)
–2.7˚F(–1.5˚C)
Room temperature – set point
Cooling : –3.6˚F(–2.0˚C)
Dry : –4.5~–3.6˚F(–2.5~–2.0˚C)
(R9857)
B
A
OFF
ON
C
3.6˚F(2.0˚C)
Room temperature – set point
0.9˚F(0.5˚C)
(R9858)
2.7˚F(1.5˚C)