SiUS04-924 Main Functions
22 Function and Control
Since the set temperature is shifted by 3.6°F (2°C) higher for 40 minutes, the compressor speed
lowers to save energy. The thermostat goes off due to the shifting of temperature so the
thermostat-off action is prohibited for 40 minutes to prevent this phenomena.
After this 40 minutes, the prohibition of the thermostat-off is cancelled and it resumes
conditions to conduct thermostat-off, depending on the room temperature. In or after this 40
minutes, if the sensor detects the human-motion detection signal, it allows the set temperature
and the fan speed to return to the original set point, maintaining normal operation.
Others The dry operation cannot command the setting temperature with a remote controller, but
internally the set temperature is shifted by 1.8°F(1°C).