Part 2. Functional Specifications
DCM014A51 Design Guide 91
5. Binary Value
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Description, Reliability, Inactive_Text, Active_Text
Writable Properties: Present_Value
Proprietary Properties: N/A
Property Range Restrictions: N/A
6. Device
a. Outdoor Unit Object
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Max_Segment_Accepted, Local_Time, Local_Date,
UTC_Offset, Daylight_Saving_Status,
APDU_Segment_Timeout, Description
Writable Properties: N/A
Proprietary Properties: N/A
Property Range Restrictions: N/A
b. Other
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Max_Segment_Accepted, Local_Time, Local_Date,
UTC_Offset, Daylight_Saving_Status,
APDU_Segment_Timeout, Active_COV_Subscriptions,
Description
Writable Properties: N/A
Proprietary Properties: N/A
Property Range Restrictions: N/A
7. Multi-state Input
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Reliability, Description, State_Text
Writable Properties: N/A
Proprietary Properties: N/A
Property Range Restrictions: N/A
8. Multi-state Output
Dynamically Creatable: No
Dynamically Deletable: No
Optional Properties Supported: Reliability, Description, State_Text
Writable Properties: Present_Value
Proprietary Properties: N/A
Property Range Restrictions: N/A