5-7
5.3 Pressure Transducer Characteristics
HPT LPT
Pressure
kPaG
Output
V
Pressure
kPaG
Output
V
Pressure
kPaG
Output
V
Pressure
kPaG
Output
V
0 0.50 1100 1.62 500 1.03 300 1.42
100 0.60 1200 1.72 400 0.72 400 1.72
200 0.70 1300 1.83 300 0.42 500 2.03
300 0.81 1400 1.93 200 0.11 600 2.34
400 0.91 1500 2.03 100 0.19 700 2.64
500 1.01 1600 2.13 0 0.50 800 2.95
600 1.11 1700 2.23 100 0.81 900 3.25
700 1.21 1800 2.34 200 1.11 1000 3.56
800 1.32 1900 2.44
900 1.42 2000 2.54
1000 1.52 2100 2.64
Input voltage
5.0V
Black
White
Red
Output voltage
LPT
HPT
5.4 Humidity Sensor Characteristics, HuS (Option)
Relative Humidity - Out-put Voltage
Relative Humidity[%] Out-put Voltage[V]±7%
00
10 0.1
20 0.2
30 0.3
40 0.4
50 0.5
60 0.6
70 0.7
80 0.8
90 0.9
100 1.0
Red
Yellow
Black
Output voltage
Input voltage
5.0V
HuS
AD070082B, 3P204826H