Check for leak from
solenoid valve during pull-down. Is the
temperature in the piping on the BSV, HSV,
and DSV outlet side high?
Does the condenser
fan rotate reverse?
Leak from solenoid valve
⇒Replace the solenoid valve
BSV: Discharged gas bypass solenoid valve
HSV: Hot gas solenoid valve
DSV: Defrost solenoid valve
Check the wiring on secondary side
of solenoid contactor for condenser fan
Is the discharge air
temperature at condenser
50˚C or higher?
Out of operation range
Restore short circuit at discharge air
Is the condenser water-cooled?
Visually check for clog
and dirt at the fin of air
cooled condenser
Clogged
⇒cleaning
Check for entering of air
referring to clause 4.1.4 (2)
Trap of air,
wrong
refrigerant
type
⇒Replace the
refrigerant
Overcharge
Entering of air,
wrong
refrigerant
type
⇒Replace the
refrigerant
Check for leak from
the solenoid valve
S-PTI alarm J101?
(P10)
Faulty compressor
⇒Replace the compressor
Overcharge⇒Replace the refrigerant
Water cooling: Water temperature is high, water cooled condenser is dirty
⇒Check the facility, or clean orreplace the water cooled condenser
Is the water piping
valve fully open?
YES
Low water level
⇒Check the facility
Is the HPS operated?
YES
NO
NO
Fully open the valve
YES
NO
YES(Reverse rotation)
NO(Normal rotation)
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO