NO
Normal
Normal
Normal
NO
Is drawn
and discharged
air reversed when
the ventilator
is opened?
Is the DCHS sensor
installed inappropriately?
Faulty
resistance of
electronic expansion
valve coil
(150Ω phase)
YES(Inappropriate)
NO(Correct)
Correct installation of sensor
YES(Inappropriate)
Replace the electronic expansion valve coil
Reset opening of EV, SMV
(Circuit breaker ON)
Is pull-down possible?
Is pull-down possible?
NO(Fan rotates normally)
Check the wiring of magnetic
contactor for evaporator fan
YES(Fan rotates reverse)
Is the current at
evaporator fan motor 0?
(on the secondary side of
magnetic contactor)
Replace the fan motor
Install the propeller fan
Is pull-down possible?
NO(Normal)
NO
Continue to next page
YES
Open the access
panel and check if
the evaporator fan
blade is removed
YES
YES
YES
YES
Manual defrost
NO
NO
NO
* See page 7-1 (type A) or
page 7-2 of TR03-1A (type E-1).