64 Daikin IM 696-4
Test Procedures
Figure 29. MicroTech II temperature sensor—temperature
(°F) vs. resistance graph
500 700 900 1100 1300 1500 1700 1900
-40
0
40
80
120
160
200
240
280
Resistance (Ohms)
Temperature (°F)
Figure 30. MicroTech II temperature sensor—temperature
(°C) vs. resistance graph
500 700 900 1100 1300 1500 1700 1900
Resistance (Ohms)
-40
-20
0
20
40
60
80
100
120
140
Temperature (°C)
Troubleshooting Communications Modules
BACnet/IP Module
For a detailed description and troubleshooting information
regarding the BACnet/IP communications module, refer to
installation and maintenance bulletin IM 703, MicroTech II
Applied Rooftop Unit Controller and Self-Contained Unit
Controller BACnet Communications Module—BACnet/IP. For
details regarding BACnet protocol data, refer to engineering
data document, ED 15060, MicroTech II Applied Rooftop Unit
Controller Protocol Information.
BACnet MS/TP Module
For a detailed description and troubleshooting information
regarding the BACnet MS/TP communications module, refer
to installation and maintenance bulletin IM 704, MicroTech II
Applied Rooftop Unit Controller and Self-Contained Unit
Controller BACnet Communications Module—BACnet/MS/TP.
For details regarding BACnet protocol data, refer to
engineering data document, ED 15060, MicroTech II Applied
Rooftop Unit Controller Protocol Information.
LonMark Modules
For a detailed description and troubleshooting information
regarding LonMark communications modules, refer to
installation and maintenance bulletin IM 702, MicroTech II
Applied Rooftop Unit Controller and Self-Contained Unit
Controller L
ONWORKS Communications Module. For details
regarding L
ONMARK protocol data, refer to engineering data
document, ED 15060, MicroTech II Applied Rooftop Unit
Controller Protocol Information.