IM 1267-7 • PRECISELINE AIR HANDLER 14 www.DaikinApplied.com
unit is level when hanging from the ceiling). Where the
surface irregularities allow the equipment to distort, shim the
appropriate base rails to straighten the unit. Distorted units can
doors and access panels and prevent proper draining of drain
pans.
Vertical Units Size 006-020 and Horizontal Units 060-100 come
with leveling legs, which can be adjusted to level the units.
Figure 16: 2-Fan Leveling Legs for Size 020 Units
Figure 17: Leveling Unit Sizes 060-100
Mounting holes on the base rails may be used to attach the
Figure 18: Mounting Rail Holes for Size 040 Units
Figure 19: Mounting Rail Holes for Sizes 060-100 Units