Appendix A. Specifications
EI.65.D4.02
116
A.2 Heat Circuit Settings – Example
Ranges
Heat curve setting With up to five curve points
Max. limiter
0 200 °C
Min. limiter
0 200 °C
Neutral zone
0 9 K
Integration time
0 999 seconds
Proportional band
1 99 K
Outdoor dependent return temperature limiter Curve setting with two points
General limit function Max or Min
Pump overrun
0 9 minutes
Pump/valve motion (once every third day at
stand-by)
ON/OFF
Night setback
10 30 °C
Total heating cut-out ON/OFF
Optimizer boost
0 100 %
Optimizer slope time
0 200 minutes
Summer cut-out
10 30 °C
Closing time at flow limit function
0 30 minutes
A.3 Hot Water Circuit Settings – Example
Ranges
Setpoint - Operation at comfort temperature
10 99 °C
Setpoint - Operation at night setback tem-
perature
10 99 °C
Cut-in difference 1 (lower tank sensor)
0 50 K
Cut-in difference 2 (upper tank sensor)
0 50 K
Max. time for hot water charging
20 200 minutes
Max. time for pump overrun
0 9 minutes
Anti-bacteria heat period
0 24 hours
Anti-bacteria heat period cut-in time
0:00 23:45
Anti-bacteria hot water temperature
1 99 °C
Setpoint for return limit temperature
10 90 °C