Thermostat
Table 15: Thermostat
Lowest Temperature Limit (°C)
Cut-out temperature at coldest position of the spindle (thermostat kNob)
Highest Temperature Limit (°C)
Cut-out temperature at warmest position of the spindle (thermostat kNob)
Lowest Temperature Dierential (K)
It the dierence between the cut-out and the cut-in at coldest position of thermo-
stat
Highest Temperature Dierential (K)
It the dierence between the cut-out and the cut-in at warmest position of thermo-
stat
Initial Pull Down:
OFF - Disable
ON - Enable
Initial Pull Down (IPD) can be used for providing faster cooling when the cabinet is
powered up with warmer inside temperature. During IPD, defrost will be skipped
until the cabinet air temperature reaches cut-out temperature or the IPD duration
expires. IPD operates only during power-up and can be enabled/disabled using it.
Initial pull down and pull down du-
ration (Hrs)
Maximum time IPD and Pull Down can run. IPD and Pull Down will terminate as
soon as this time expires, regardless of the cabinet air temperature.
Initial pull down and pull down ini-
tiate temperature (°C)
It indicates the temperature at which IPD or Pull Down will be initiated:
• At Power up: If the cabinet air temp. > Pit for more than 5 minutes it will trigger
the Initial Pull Down
• During Normal operation: if the cabinet air temp stays above Pit>1hr it will trig-
ger the Pull Down
Pull Down Oset temperature (°C)
This parameter sets the cut out temperature oset during Pull-down cycle to ach-
ieve more cooling. When set as “0” pull down feature is disabled.
Compressor
Table 16: Compressor
To prevent the compressor from frequent cut-outs, it ensures that the compressor
runs for at least the specied time. It overrides the cut-out temperature. (Tip: setting
it too high could lead to unneccessary deep temperatures)
To prevent the compressor from frequent cut-ins, it ensures that the compressor re-
mains o for at least the specied time under this parameter. It overrides the cut-in
temperatures. (Tip: setting it too high could lead to unneccessary warm tempera-
tures)
Compressor stop delay on door
open (Sec.)
It sets the delay in stopping the compressor when the door is opened. If set to “0”,
the compressor stops immediately. If set to “999”, the function will be disabled and
the compressor will not be stopped
System Resume after door open
(Mins)
If the door is kept open for a long time, the compressor and the fan will resume after
this time, if they switched o due to an open door. (Note: 'Srt' must be always great-
er than' Cdd' and 'Fdt'). If Srt=0, the system resume feature is disabled and the sys-
tem will resume only when the door is closed.
Second Compressor start delay
(Sec.)
Delay time for starting the second compressor in dual compressor control
This is the delay in seconds between power-on and the output relays being activa-
ted
Alarm
Table 17: Alarm
Low temp Alarm limit (°C)
If the cabinet air temperature goes below this value, a low temperature alarm will be
raised (all these alarm statuses can be viewed only in KoolProg)
High temp Alarm limit (°C)
If the cabinet air temperature goes above this value, a low temperature alarm will be
raised
Low temp Alarm delay (Mins)
Time delay to raise alarm once the low temperature alarm limit is reached
High temp Alarm delay (Mins)
Time delay to raise alarm once the high temperature alarm limit is reached
Refrigeration controller, type EET series
© Danfoss | Climate Solutions | 2023.07 BC320944106159en-000301 | 22