Fan Delay After Defrost (Sec.) (appli-
cable only for EETc 2x series)
Denes delay in switching “ON” the fan from compressor start after defrost to avoid
warm air circulation
Fan Start Temperature after defrost
(°C) (applicable only for EETc 2x ser-
ies)
It determines at what evaporator temperature the fan will start after a defrost cycle.
If the time set in “Fdd” occurs before the temperature set in “Ftd”, the fan will start in
line with “Fdd”. If the temperature set in “Ftd” occurs rst, then the fan will start in
line with “Ftd”
Fan ON during Defrost (applicable
only for EETc 2x series)
Denes the status of the fan during defrost. Set to "Yes", the fan will run during de-
frost cycles and set to "No", the fan will be kept o during defrost cycles
Initial Defrost Interval (Mins)
The initial defrost interval determines the time for rst defrost after power-up. The
initial defrost is mainly intended for factory testing of the defrost functionality and
can be set to expire after a number compressor cycles according to the setting of
parameter idd.
Initial defrost duration (Cycles)
The initial defrost duration is the number of compressor cycles after which initial de-
frost is deactivated.
“0” : No initial defrost
“1-998” : number of compressor cycles before deactivation
“999” : initial defrost always active.
Fan
Table 9: Fan (applicable only for EETc 2x series)
Fan
(applicable only for EETc 2x series)
Denes the fan control method:
“FAo” : fan always on
“FFc” : fan follows compressor (fan runs only when compressor is ON)
“FPL” : fan cycling (fan cycling during compressor o cycle)
Time delay to start the fan after compressor cut-in
Time delay to stop the fan after compressor cut-out
If fan control method is selected as "FPL", it denes the fan ON time during compres-
sor OFF cycle.
If fan control method is selected as "FPL", it denes the fan OFF time during com-
pressor OFF cycle.
Fan stop delay on door open (Sec.)
The delay to stop the fan after the door has been opened:
“0” : fan stop immediately when door opens
“1-998” : delay for fan stop after door opens
“999” : fan keep running all the time, fan does not stop while door is opened
Fan Minimum Stop Time (Sec.)
Minimum time that the fan must stop whenever it is switched o.
Fan Limit Temperature (°C)
This function prevents the evaporator fan from operating if the evaporator tempera-
ture is above the fan limit temperature. If the defrost sensor registers a higher tem-
perature than the one set here, the fan will be stopped to avoid the warm air circula-
tion in the cabinet. The fan will restart when the evaporator temperature goes 2 °C
less than FLt (FLt - 2 °C). It is active only when the evaporator sensor is congured.
ECO Management
Table 10: ECO Management
ECO mode is active or not. If “No” is selected all other settings related to ECO mode
are not active.
Denes
oset temperature during ECO mode. Oset can be positive or negative.
ECO setpoint = setpoint + Eto
Controller will enter ECO mode, if the door are not opened for a time longer than
Edd.