Surroundings:
Enclosure type A IP 20/Chassis, IP 21kit/Type 1, IP55/Type12, IP 66/Type12
Enclosure type B1/B2 IP 21/Type 1, IP55/Type12, IP 66/12
Enclosure type B3/B4 IP20/Chassis
Enclosure type C1/C2 IP 21/Type 1, IP55/Type 12, IP66/12
Enclosure type C3/C4 IP20/Chassis
Enclosure type D1/D2/E1 IP21/Type 1, IP54/Type12
Enclosure type D3/D4/E2 IP00/Chassis
Enclosure type F1/F3 IP21, 54/Type1, 12
Enclosure type F2/F4 IP21, 54/Type1, 12
Enclosure kit available enclosure type D
IP21/NEMA 1/IP 4
X
on top of enclosure
Vibration test enclosure A, B, C 1.0 g
Vibration test enclosure D, E, F 0.7 g
Relative humidity 5% - 95% (IEC 721-3-3; Class 3K3 (non-condensing) during operation
Aggressive environment (IEC 60068-2-43) H
2
S test
class Kd
Test method according to IEC 60068-2-43 H2S (10 days)
Ambient temperature (at 60 AVM switching mode)
- with derating max. 55° C
1)
- with full output power of typical EFF2 motors (up to 90% output current) max. 50 ° C
1)
- at full continuous FC output current max. 45 ° C
1)
1)
For more information on derating see the Design Guide, section on Special Conditions.
Minimum ambient temperature during full-scale operation 0 °C
Minimum ambient temperature at reduced performance - 10 °C
Temperature during storage/transport -25 - +65/70 °C
Maximum altitude above sea level without derating 1000 m
Maximum altitude above sea level with derating 3000 m
Derating for high altitude, see section on special conditions
EMC standards, Emission EN 61800-3, EN 61000-6-3/4, EN 55011, IEC 61800-3
EMC standards, Immunity
EN 61800-3, EN 61000-6-1/2,
EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6
See section on special conditions!
Control card performance:
Scan interval : 5 ms
Control card, USB serial communication:
USB standard 1.1 (Full speed)
USB plug USB type B “device” plug
CAUTION!
Connection to PC is carried out via a standard host/
device USB cable.
The USB connection is galvanically isolated from the
supply voltage (PELV) and other high-voltage terminals.
The USB connection is
not galvanically isolated from
protection earth. Use only isolated laptop/PC as connec-
tion to the USB connector on frequency converter or an
isolated USB cable/converter.
Specifications
VLT
®
HVAC Drive Operating Instructions
MG.11.AD.02 - VLT
®
is a registered Danfoss trademark 143
9
9

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 100 Series and is the answer not in the manual?

Danfoss FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 100 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals