Unsuccessful AMA
1. The frequency converter enters into alarm mode. A
description of the alarm can be found in the Trouble-
shooting section.
2. "Report Value” in the [Alarm Log] shows the last
measuring sequence carried out by the AMA, before
the frequency converter entered alarm mode. This
number along with the description of the alarm will
assist troubleshooting. If contacting Danfoss Service,
make sure to mention number and alarm descrip-
tion.
NOTE
Unsuccessful AMA is often caused by incorrectly entered
motor name plate data or too big difference between
the motor power size and the frequency converter
power size.
Step 4: Set speed limit and ramp time
Set up the desired limits for speed and ramp time.
Par. 3-02 Minimum Reference
Par. 3-03 Maximum Reference
Par. 4-11 Motor Speed Low Limit [RPM] or par. 4-12 Motor Speed Low Limit [Hz]
Par. 4-13 Motor Speed High Limit [RPM] or par. 4-14 Motor Speed High Limit [Hz]
Par. 3-41 Ramp 1 Ramp Up Time Ramp-up Time 1 [s]
Par. 3-42 Ramp 1 Ramp Down Time Ramp-down Time 1 [s]
See the section How to programme the frequency converter,
Quick Menu Mode for an easy set-up of these parameters.
Electrical Installation
VLT
®
HVAC Drive Operating Instructions
46 MG.11.AD.02 - VLT
®
is a registered Danfoss trademark
4
4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 100 Series and is the answer not in the manual?

Danfoss FC 100 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 100 Series
CategoryMedia Converter
LanguageEnglish

Related product manuals