3-03 Maximum Reference
Range: Function:
Applica-
tion
depend-
ent
*
[Applica-
tion
depend-
ant]
Enter the maximum acceptable value for
the remote reference. The Maximum
Reference value and unit matches the
configuration choice made in
par. 1-00 Configuration Mode and
par. 20-12 Reference/Feedback Unit,
respectively.
NOTE
If operating with par. 1-00 Config-
uration Mode set for Closed Loop
[3], par. 20-14 Maximum
Reference/Feedb. must be used.
3-10 Preset Reference
Array [8]
Range: Function:
0.00
%
*
[-100.00 -
100.00 %]
Enter up to eight different preset references
(0-7) in this parameter, using array program-
ming. The preset reference is stated as a
percentage of the value Ref
MAX
(par. 3-03 Maximum Reference, for closed loop
see par. 20-14 Maximum Reference/Feedb.).
When using preset references, select Preset
ref. bit 0 / 1 / 2 [16], [17] or [18] for the
corresponding digital inputs in parameter
group 5-1* Digital Inputs.
3-11 Jog Speed [Hz]
Range: Function:
Application
dependent
*
[Application
dependant]
The jog speed is a fixed output
speed at which the frequency
converter is running when the
jog function is activated.
See also par. 3-80 Jog Ramp
Time.
Application
dependent
*
[Application
dependant]
3-15 Reference 1 Source
Option: Function:
Select the reference input to be used
for the first reference signal.
Par. 3-15 Reference 1 Source,
par. 3-16 Reference 2 Source and
par. 3-17 Reference 3 Source define up
to three different reference signals.
The sum of these reference signals
defines the actual reference.
This parameter cannot be adjusted
while the motor is running.
[0] No function
[1]
*
Analog input 53
[2] Analog input 54
[7] Pulse input 29
[8] Pulse input 33
[20] Digital pot.meter
[21] Analog input X30/11
[22] Analog input X30/12
[23] Analog Input X42/1
[24] Analog Input X42/3
[25] Analog Input X42/5
[29] Analog Input X48/2
[30] Ext. Closed Loop 1
[31] Ext. Closed Loop 2
[32] Ext. Closed Loop 3
How to Programme the Frequ...
VLT
®
HVAC Drive Operating Instructions
74 MG.11.AD.02 - VLT
®