0-51 Set-up Copy
Option: Function:
[0]
*
No copy No function
[1] Copy to set-
up 1
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 1.
[2] Copy to set-
up 2
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 2.
[3] Copy to set-
up 3
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 3.
[4] Copy to set-
up 4
Copies all parameters in the present
Programming Set-up (defined in
0-11 Programming Set-up) to Set-up 4.
[9] Copy to all Copies the parameters in the present set-up
over to each of the set-ups 1 to 4.
3.2.7 0-6* Password
0-60 Main Menu Password
Range: Function:
100 N/A
*
[0 - 999 N/
A]
Define the password for access to the main
menu via the [Main Menu] key. If
0-61 Access to Main Menu w/o Password is
set to Full access [0], this parameter will be
ignored.
0-61 Access to Main Menu w/o Password
Option: Function:
[0]
*
Full access Disables password defined in 0-60 Main
Menu Password.
[1] LCP: Read only Prevent unauthorized editing of main menu
parameters.
[2] LCP: No access Prevent unauthorized viewing and editing of
main menu parameters.
[3] Bus: Read only Read-only functions for parameters on the
serial communication bus and/or FC
standard bus.
[4] Bus: No access No access to parameters is allowed via the
serial communication bus and/or FC
standard bus.
[5] All: Read only Read-only function for parameters on the
LCP, serial communication bus or FC
standard bus.
[6] All: No access No access from LCP, serial communication
bus or FC standard bus is allowed.
If Full access [0] is selected then 0-60 Main Menu Password,
0-65 Personal Menu Password and 0-66 Access to Personal
Menu w/o Password will be ignored.
0-65 Quick Menu Password
Range: Function:
200
*
[-9999 -
9999 ]
Define the password for access to the quick
menu via the [Quick Menu] key. If 0-66 Access
to Quick Menu w/o Password is set to Full
access [0], this parameter will be ignored.
0-66 Access to Quick Menu w/o Password
Option: Function:
[0]
*
Full access Disables the password defined in 0-65 Quick
Menu Password.
[1] LCP: Read only Prevents unauthorized editing of quick
menu parameters.
[2] LCP: No access Prevents unauthorized viewing and editing
of quick menu parameters.
[3] Bus: Read only Read only functions for quick menu
parameters on serial communication bus
and/ or FC standard bus.
[4] Bus: No access No access to quick menu parameters is
allowed via serial communication bus and/
or FC standard bus.
[5] All: Read only read only function for quick menu
parameters on LCP, serial communication
bus or FC standard bus.
[6] All: No access No access from LCP, serial communication
bus or FC standard bus is allowed.
If 0-61 Access to Main Menu w/o Password is set to Full access
[0], then this parameter will be ignored.
0-67 Bus Password Access
Range: Function:
0
*
[0 - 9999 ] Writing to this parameter enables users to unlock
the adjustable frequency drive from bus/ MCT10.
Parameter Descriptions FC 300 Programming Guide
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark 3-11
3
3