3.2.5 0-4* LCP Keypad
Enable, disable and password protect individual keys on the
LCP.
0-40 [Hand on] Key on LCP
Option: Function:
[0] Disabled No effect when [Hand on] is pressed. Select
[0] Disabled to avoid accidental start of the
drive in Hand on mode.
[1]
*
Enabled The LCP switches to Hand on mode directly
when [Hand on] is pressed.
[2] Password After pressing [Hand on], a password is
required. If par. 0-40 is included in My
Personal Menu, define the password in par.
0-65, Personal Menu Password. Otherwise,
define the password in par. 0-60, Main Menu
Password
[3] Hand Off/On When [Hand on] is pressed once, the LCP
switches to Off mode. When pressed again,
the LCP switches to Hand on mode.
[4] H off/on w.
passw.
Same as [3] but a password is required (see
[2]).
0-41 [Off] Key on LCP
Option: Function:
[0]
*
Disabled Avoids accidental stop of the adjustable frequency
drive.
[1]
*
Enabled
[2] Password Avoids unauthorized stop. If 0-41 [Off] Key on LCP is
included in the quick menu, then define the
password in 0-65 Quick Menu Password.
0-42 [Auto on] Key on LCP
Option: Function:
[0]
*
Disabled Avoid accidental start of the adjustable frequency
drive in auto mode.
[1]
*
Enabled
[2] Password Avoids unauthorized start in auto mode. If
0-42 [Auto on] Key on LCP is included in the quick
menu, then define the password in 0-65 Quick
Menu Password.
0-43 [Reset] Key on LCP
Option: Function:
[0]
*
Disabled No effect when [Reset] is pressed. Avoids
accidental alarm reset.
[1]
*
Enabled
[2] Password Avoids unauthorized resetting. If
0-43 [Reset] Key on LCP is included in the
quick menu, then define the password in
0-65 Quick Menu Password.
[7] Enabled
without OFF
Resets the drive without setting it in Off
mode.
[8] Password
without OFF
Resets the drive without setting it in Off
mode. A password is required when
pressing [Reset] (see [2]).
3.2.6 0-5* Copy/Save
Copy parameter settings between set-ups and to/from the
LCP.
0-50 LCP Copy
Option: Function:
[0]
*
No copy
[1] All to LCP Copies all parameters in all set-ups from
the adjustable frequency drive memory
to the LCP memory.
[2] All from LCP Copies all parameters in all set-ups from
the LCP memory to the adjustable
frequency drive memory.
[3] Size indep. of LCP Copy only the parameters that are
independent of the motor size. The
latter selection can be used to program
several adjustable frequency drives with
the same function without disturbing
motor data.
[4] File from MCO to
LCP
[5] File from LCP to
MCO
[6] Data from DYN to
LCP
[7] Data from LCP to
DYN
This parameter cannot be adjusted while the motor is
running.
Parameter Descriptions FC 300 Programming Guide
3-10 MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Series and is the answer not in the manual?

Danfoss FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals