EasyManuals Logo
Home>Danfoss>DC Drives>FC 300 Series

Danfoss FC 300 Series User Manual

Danfoss FC 300 Series
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #42 background imageLoading...
Page #42 background image
1-62 Slip Compensation
Range: Function:
Application
dependent
*
[-500 -
500 %]
Enter the % value for slip compensation
to compensate for tolerances in the value
of n
M,N
. Slip compensation is calculated
automatically, i.e., on the basis of the
rated motor speed n
M,N
.
This function is not active when
1-00 Configuration Mode is set to Speed
closed-loop [1] or Torque [2] Torque
control with speed feedback or when
1-01 Motor Control Principle is set to U/f [0]
special motor mode.
1-63 Slip Compensation Time Constant
Range: Function:
Application
dependent
*
[0.05 - 5.00
s]
Enter the slip compensation
reaction speed. A high value results
in slow reaction, and a low value
results in quick reaction. If low-
frequency resonance problems
arise, use a longer time setting.
1-64 Resonance Dampening
Range: Function:
100 %
*
[0 - 500
%]
Enter the resonance dampening value. Set
1-64 Resonance Dampening and
1-65 Resonance Dampening Time Constant to
help eliminate high-frequency resonance
problems. To reduce resonance oscillation,
increase the value of 1-64 Resonance
Dampening.
1-65 Resonance Dampening Time Constant
Range: Function:
5 ms
*
[5 - 50 ms] Set 1-64 Resonance Dampening and
1-65 Resonance Dampening Time Constant to
help eliminate high-frequency resonance
problems. Enter the time constant that
provides the best dampening.
1-66 Min. Current at Low Speed
Range: Function:
100
%
*
[Application
dependant]
Enter the minimum motor current at low
speed, see 1-53 Model Shift Frequency.
Increasing this current improves motor
torque at low speed.
1-66 Min. Current at Low Speed is enabled
when 1-00 Configuration Mode = Speed
open-loop [0] only. The adjustable frequency
drive runs with constant current through
motor for speeds below 10 Hz.
1-66 Min. Current at Low Speed
Range: Function:
For speeds above 10 Hz, the motor flux
model in the adjustable frequency drive
controls the motor. 4-16 Torque Limit Motor
Mode and / or 4-17 Torque Limit Generator
Mode automatically adjust 1-66 Min. Current
at Low Speed. The parameter with the
highest value adjusts 1-66 Min. Current at
Low Speed. The current setting in 1-66 Min.
Current at Low Speed is composed of the
torque generating current and the
magnetizing current.
Example: Set 4-16 Torque Limit Motor Mode
to 100% and set 4-17 Torque Limit Generator
Mode to 60%. 1-66 Min. Current at Low Speed
automatically adjusts to about 127%,
depending on the motor size.
This parameter is available for the FC 302
only.
1-67 Load Type
Option: Function:
[0]
*
Passive load For conveyers, fan and pump applications.
[1] Active load For hoisting applications, used in slip compen-
sation at low speed. When Active Load [1] is
selected, set 1-66 Min. Current at Low Speed to a
level which corresponds to maximum torque.
This parameter is available for the FC 302 only.
1-68 Minimum Inertia
Range: Function:
Application
dependent
*
[Application
dependant]
Needed for average inertia
calculation. Enter the minimum
moment of inertia of the
mechanical system. 1-68 Minimum
Inertia and 1-69 Maximum Inertia
are used for pre-adjustment of the
proportional gain in the speed
control, see 30-83 Speed PID Propor-
tional Gain.
This parameter is available for the
FC 302 only.
This parameter cannot be adjusted while motor is running.
Parameter Descriptions FC 300 Programming Guide
3-20 MG.33.MA.22 - VLT
®
is a registered Danfoss trademark
3
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss FC 300 Series and is the answer not in the manual?

Danfoss FC 300 Series Specifications

General IconGeneral
BrandDanfoss
ModelFC 300 Series
CategoryDC Drives
LanguageEnglish

Related product manuals