EasyManua.ls Logo

Danfoss FC 300 Series

Danfoss FC 300 Series
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
[72] Logic Rule 2 See par. group 13-4*. If Logic Rule 2 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[73] Logic Rule 3 See par. group 13-4*. If Logic Rule 3 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[74] Logic Rule 4 See par. group 13-4*. If Logic Rule 4 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[75] Logic Rule 5 See par. group 13-4*. If Logic Rule 5 is
evaluated as TRUE, the output will go
high. Otherwise, it will be low.
[80] SL Digital Output
A
See 13-52 SL Controller Action. The output
will go high whenever the Smart Logic
Action [38] Set dig. out. A high is
executed. The output will go low
whenever the Smart Logic Action [32] Set
dig. out. A low is executed.
[81] SL Digital Output
B
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [39] Set dig. out. A high is
executed. The input will go low
whenever the Smart Logic Action [33] Set
dig. out. A low is executed.
[82] SL Digital Output
C
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [40] Set dig. out. A high is
executed. The input will go low
whenever the Smart Logic Action [34] Set
dig. out. A low is executed.
[83] SL Digital Output
D
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [41] Set dig. out. A high is
executed. The input will go low
whenever the Smart Logic Action [35] Set
dig. out. A low is executed.
[84] SL Digital Output
E
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [42] Set dig. out. A high is
executed. The input will go low
whenever the Smart Logic Action [36] Set
dig. out. A low is executed.
[85] SL Digital Output
F
See 13-52 SL Controller Action. The input
will go high whenever the Smart Logic
Action [43] Set dig. out. A high is
executed. The input will go low
whenever the Smart Logic Action [37] Set
dig. out. A low is executed.
[120] Local reference
active
Output is high when 3-13 Reference Site =
[2] Local or when 3-13 Reference Site = [0]
Linked to hand auto at the same time as
the LCP is in hand on mode.
Reference site set
in 3-13 Reference
Site
Local
referenc
e
active
[120]
Remote
reference
active
[121]
Reference site:
Local
3-13 Reference Site
[2]
10
Reference site:
Remote
3-13 Reference Site
[1]
01
Reference site:
Linked to Hand/
Auto
Hand 1 0
Hand -> off 1 0
Auto -> off 0 0
Auto 0 1
[121] Remote
reference active
Output is high when 3-13 Reference Site =
Remote [1] or Linked to hand/auto [0]
while the LCP is in [Auto on] mode. See
above.
[122] No alarm Output is high when no alarm is present.
[123] Start command
active
Output is high when there is an active
start command (i.e., via digital input bus
connection or [Hand on] or [Auto on]),
and no stop or start command is active.
[124] Running reverse Output is high when the adjustable
frequency drive is running counter
clockwise (the logical product of the
status bits ‘running’ AND ‘reverse’).
[125] Drive in hand
mode
Output is high when the adjustable
frequency drive is in hand on mode (as
indicated by the LED light above [Hand
on]).
[126] Drive in auto
mode
Output is high when the adjustable
frequency drive is in hand on mode (as
indicated by the LED light above [Auto
on]).
5-30 Terminal 27 Digital Output
Option: Function:
[0]
*
No operation Functions are described under 5-3* Digital
Outputs
5-31 Terminal 29 Digital Output
Option: Function:
[0]
*
No operation Functions are described under 5-3* Digital
Outputs
This parameter only applies to the FC 302
Parameter Descriptions FC 300 Programming Guide
MG.33.MA.22 - VLT
®
is a registered Danfoss trademark 3-55
3
3

Table of Contents

Related product manuals