Operating Instructions
Metasys N2
VLT® HVAC Drive FC 102
VLT® AQUA Drive FC 202

Questions and Answers

  • J
    john63Aug 19, 2025
    What to do if I get Alarm 68, Safe Stop on my Danfoss Controller?
    • M
      Molly SchroederAug 20, 2025
      To resume normal operation of the Danfoss Controller after Alarm 68 (Safe Stop), apply 24 V DC to terminal 37 and then send a reset signal. This can be done via bus, digital I/O, or by pressing the Reset button.
  • M
    Margaret Stone MDAug 22, 2025
    What to do if Danfoss Metasys N2 power off?
    • J
      Jeremy AguilarAug 22, 2025
      If your Danfoss DC Drives show 'Power Off', it could be due to either no power supply or no link on the corresponding port. Ensure that the power is on and the link is active.
  • H
    Heather BatesAug 25, 2025
    Why Danfoss Metasys N2 DC Drives power on with red light?
    • C
      Chris UnderwoodAug 25, 2025
      If your Danfoss DC Drives show 'Power On' and the indicator is red, this typically indicates an IP Address Conflict. Resolve the IP conflict.
  • A
    Amy FinleyAug 26, 2025
    What to do if Danfoss Control Unit is in operation but not responding to control commands?
    • M
      Michael RodriguezAug 26, 2025
      If the Danfoss Control Unit is running but ignoring control commands, try using the [Hand On] control or reference values from the LCP.
  • M
    Michele Yoder MDAug 27, 2025
    How to fix Danfoss Control Unit that does not react to any control signal?
    • J
      Juan LeeAug 28, 2025
      If the Danfoss Control Unit isn't responding to any control signals, try pressing either the [Auto On] or [Hand On] button.
  • C
    Courtney BanksAug 29, 2025
    What to do if Danfoss Metasys N2 show DC Overvoltage warning?
    • C
      Claudia OrtizAug 30, 2025
      If your Danfoss DC Drives unit displays a DC Overvoltage warning or alarm, it means the DC-link voltage has exceeded its limit, potentially causing the drive to trip. To resolve this, consider these steps: * Connect a brake resistor. * Extend the ramp time. * Change the ramp type. * Activate the functions in parameter 2-10 Brake Function. * Increase parameter 14-26 Trip Delay at Inverter Fault. If the issue arises during a power sag, explore using kinetic back-up (parameter 14-10 Mains Failure).
  • Z
    zyoungSep 1, 2025
    What to do if Danfoss Metasys N2 display Inverter Overload warning?
    • N
      npenaSep 1, 2025
      If your Danfoss DC Drives unit is showing an inverter overload warning or alarm, it means the drive has been running with more than 100% overload for an extended period and is at risk of shutting down. Here's what you can do: * Compare the output current displayed on the LCP with the drive's rated current. * Compare the output current on the LCP with the measured motor current. * Monitor the thermal drive load on the LCP. If running above the drive's continuous current rating, the counter increases; if running below, it decreases.
  • B
    barkerjenniferSep 3, 2025
    What to do if Danfoss Metasys N2 DC Drives show Mains Phase Loss alarm?
    • M
      Megan GonzalezSep 3, 2025
      If your Danfoss DC Drives unit is showing a Mains Phase Loss warning or alarm, it indicates a missing phase on the supply side or an excessive mains voltage imbalance. This message can also appear due to a fault in the input rectifier. To address this, check the supply voltage and supply currents to the drive.
  • R
    Rachel KingSep 7, 2025
    How to deactivate Safe Stop on Danfoss DC Drives?
    • D
      Derek SotoSep 7, 2025
      If the Safe Stop is activated on your Danfoss DC Drives, it means that Safe Torque Off (STO) has been engaged. To resume normal operation, apply 24 V DC to terminal 37, and then send a reset signal via bus, digital input, or by pressing the Reset button.
  • A
    Alexandria HatfieldSep 8, 2025
    What to do if Danfoss Metasys N2 display Live Zero Error?
    • B
      Brett WoodsSep 9, 2025
      The 'Live Zero Error' warning or alarm on your Danfoss DC Drives appears if programmed in parameter 6-01 Live Zero Timeout Function and the signal on one of the analog inputs is less than 50% of the minimum value programmed for that input. Check the connections on all analog mains terminals. Also, check control card terminals 53 and 54 for signals, using terminal 55 as common. Ensure that the drive programming and switch settings match the analog signal type.