3.1.5 Internal Floating Point (ADF)
NPA Unit Description Range FC Par. Number
0 - Max value of custom readout 0-32
1 - Min value of custom readout 0-31
13 A
Motor Current(I
M.N
)
1-24
14 RPM Motor nom. Speed 1-25
16 % Resonance damping 1-64
18 Sec Start delay 1-71
19 % Preheat DC-current 2-00
20 % DC brake current 2-01
21 Sec DC braking time 2-02
22 Hz DC brake cut-in frequency 2-03
29 - Max output Frequency 4-19
34 Sec Ramp Up Time 3-41
35 Sec Ramp Down Time 3-42
36 Hz Jog Frequency 3-11
37 % Digital Reference 1 3-10:0
38 % Digital Reference 2 3-10:1
39 % Digital Reference 3 3-10:2
40 % Digital Reference 4 3-10:3
41 A Current Limit 4-18
42 Hz Frequency 1. Bypass start 4-61:0
43 Hz Frequency 1. Bypass stop 4-63:0
44 Hz Frequency 2. Bypass start 4-61:1
45 Hz Frequency 2. Bypass stop 4-63:1
46 Hz Frequency 3. Bypass start 4-61:2
47 A Frequency 3. Bypass stop 4-63:2
48 A Frequency 4. Bypass start 4-61:3
49 Hz Frequency 4. Bypass stop 4-63:3
50 A
Warning Current Low(I
LOW
)
4-50
51 A
Warning Current High (I
HIGH
)
4-51
52 Hz
Warning Freq. Low(F
LOW
)
4-52
53 Hz
Warning Freq. High(F
HIGH
)
4-53
54 Unit
Warning Low Ref.(Ref
LOW
)
4-54
55 Unit
Warning High Ref.(Ref
HIGH
)
4-55
56 Unit
Warning Low FB.(FB
LOW
)
4-56
57 Unit
Warning High FB.(FB
HIGH
)
4-57
60 V Terminal 53 min scale V 6-10
61 V Terminal 53 max scale V 6-11
62 V Terminal 53 min scale mA 6-12
63 V Terminal 53 max scale mA 6-13
64 A Terminal 54 min. scale V 6-20
65 V Terminal 54 max. scale V 6-21
66 V Terminal 54 min. scale mA 6-22
67 A Terminal 54 max. scale mA 6-23
68 Hz Terminal 42 output puls scale 5-62
69 Hz Terminal 45 output puls scale 5-65
70 mSec CC Relay 1 ON Delay 5-41:0
71 mSec CC Relay 1 ON Delay 5-42:0
72 mSec CC Relay 1 ON Delay 5-41:1
73 Sec CC Relay 1 ON Delay 5-42:1
Appendix
VLT
®
Metasys
MG.11.G2.02 - VLT
®
is a registered Danfoss trademark 25