Internal Floating Point (ADF), continued..
NPA Unit Description Range FC Par. Number
80 Sec No Flow Timer 0-600 22-24
81 Sec Dry Pump Timer 0-600 22-27
82 Sec Minimum Run Time 0-600 22-40
83 Hz Minimum Sleep Time 0-600 22-41
84 % Boost setpoint -100% - +100% 22-45
85 Hz Wake-up Speed Par. 4-12 to 4-14 22-43
86 Sec Max Boost Time 0-600 22-46
87 kHz Switch Frequency 14-01
88 Unit Set point 1 20-21
89 Unit Set point 2 20-22
90 Hz PID Start Frequency 20-83
91 - PID Proportional Gain 20-93
92 Sec PID Integration Time 20-94
93 Sec PID Differentiation Time 20-95
94 - PID D-gain Limit 20-96
95 Unit Set Point 3 20-23
100 - Control Timeout Function 8-04
101 - Control Timeout Time 8-03
110 Sec Option B Relay 1 ON Delay 0.01 to 600.00 5-41:6
111 Sec Option B Relay 1 OFF Delay 0.01 to 600.00 5-42:6
112 Sec Option B Relay 2 ON Delay 0.01 to 600.00 5-41:7
113 Sec Option B Relay 2 OFF Delay 0.01 to 600.00 5-42:7
114 Sec Option B Relay 3 ON Delay 0.01 to 600.00 5-41:8
115 Sec Option B Relay 3 OFF Delay 0.01 to 600.00
120 V Analogue Input, GPIO option X30/11, Low Voltage 6-30
121 V Analogue Input, GPIO option X30/11, High Voltage 6-31
122 V Analogue Input, GPIO option X30/12 Low Voltage 6-40
123 V Analogue Input, GPIO option X30/12, High Voltage 6-41
124 V Analogue Input, IO X42/1, Low Voltage 0.07 to 10.00 26-10
125 V Analogue Input, IO option X42/1, High Voltage 0.07 to 10.00 26-11
126 V Analogue Input, IO option X42/3, Low Voltage 0.07 to 10.00 26-20
127 V Analogue Input, IO option, X42/3, High Voltage 0.07 to 10.00 26-21
128 V Analogue Input, IO option X42/5, Low Voltage 0.07 to 10.00 26-30
129 V Analogue Input, IO option X42/5, High Voltage 0.07 to 10.00 26-31
130 % Analogue Output 42 Timeout Preset 6-54
131 % Analogue Output, GPIO option X30/8, Timeout Preset 6-64
132 % Analogue Output, IO option X42/7, Timeout Preset 0.00 to 100.00 26-54
133 % Analogue Output, IO option X42/9, Timeout Preset 0.00 to 100.00 26-64
134 % Analogue Output, IO option X42/11, Timeout Preset 0.00 to 100.00 26-74
140 Ext. 1 Setpoint 21-15
141 Ext. 1 Proportinal Gain 21-21
142 Ext. 1 Integral Gain 21-22
143 Ext. 1 Differentation Time 21-23
144 Ext. 2 Setpoint 21-35
145 Ext. 2 Proportinal Gain 21-41
146 Ext. 2 Integral Time 21-42
147 Ext. 2 Differentation Time 21-43
Appendix
VLT
®
Metasys
26 MG.11.G2.02 - VLT
®