3.1.4 Binary Outputs (BO)
NPA Unit Description
Range
1)
FC Par. Number
0 2 DC Brake Inverse 0=Active, 1=Not Active
Par. 16-00 Control Word
1 3 Coast Inverse 0=Active, 1=Not Active
2 4 Stop Inverse 0=Active, 1=Not Active
3 5 Freeze Output Inverse 0=Active, 1=Not Active
4 6 Start 0=Not active, 1=Active
5 7 Stop 0=Not active, 1=Active
6 8 Jog 0=Not active, 1=Active
8 11 Relay01 0=Not active, 1=Active
9 12 Relay02 0=Not active, 1=Active
10 15 Reversing 0=Not active, 1=Active
11 13 Setup LSB 0=Not active, 1=Active
12 14 Setup MSB 0=Not active, 1=Active
13 0 Preset ref. LSB 0=Not active, 1=Active
14 1 Preset ref. MSB 0=Not active, 1=Active
20 0 Output Terminal 27 0=Not active, 1=Active
Par. 5-90 Digital & Relay Bus
Control
21 1 Output Terminal 29 0=Not active, 1=Active
22 2 Output Terminal X30/6 0=Not active, 1=Active
23 3 Output Terminal X30/7 0=Not active, 1=Active
24 4 CC Relay 1 0=Not active, 1=Active
25 5 CC Relay 2 0=Not active, 1=Active
26 6 Option B Relay 1 0=Not active, 1=Active
27 7 Option B Relay 2 0=Not active, 1=Active
28 8 Option B Relay 3 0=Not active, 1=Active
29 9 Reserved 0=Not active, 1=Active
30 10 Reserved 0=Not active, 1=Active
31 11 Reserved 0=Not active, 1=Active
32 12 Reserved 0=Not active, 1=Active
33 13 Reserved 0=Not active, 1=Active
34 14 Reserved 0=Not active, 1=Active
35 15 Reserved 0=Not active, 1=Active
36 16 Option C Relay 1 0=Not active, 1=Active
37 17 Option C Relay 2 0=Not active, 1=Active
38 18 Option C Relay 3 0=Not active, 1=Active
39 19 Option C Relay 4 0=Not active, 1=Active
40 20 Option C Relay 5 0=Not active, 1=Active
41 21 Option C Relay 6 0=Not active, 1=Active
42 22 Option C Relay 7 0=Not active, 1=Active
43 23 Option C Relay 8 0=Not active, 1=Active
44 24 Reserved 0=Not active, 1=Active
45 25 Reserved 0=Not active, 1=Active
46 26 Reserved 0=Not active, 1=Active
47 27 Reserved 0=Not active, 1=Active
48 28 Reserved 0=Not active, 1=Active
49 29 Reserved 0=Not active, 1=Active
50 30 Reserved 0=Not active, 1=Active
52 ECB Activate 31-19
60 No Flow Detection 0=Not active, 1=Active 22-21
61
Enable Interval
between starts
0=Disable, 1=Enable 22-75
1)
The values in BOLD are the default values.