2.1.13 Binary Output Commands (Acknowledged)
VLT
Response
Command Subcom-
mand
Region NPA Object
no.
Attribute
No.
Attribute Message Type Comments
ACK 1 - 4 0-10 1 Byte Read Binary
Output
Read structure attributes associated
with each individual point
ACK 1 - 4 0-10 2 Byte Read Binary
Output
Read structure attributes associated
with each individual point
ACK 2 - 4 0-10 1 Byte Write Binary
Output
Write to Object Configuration attrib-
ute associated with each
individual point
ACK 7 2 4 0-10 - Byte(0/1) Override Binary
Output
Write to binary output current state
(VLT control word)
ACK 7 2 4 0-10 - Byte(0/1) Override Binary
Output
Write to binary output current state
(VLT control word)
ACK 7 3 4 0-10 - - Override Release Set the current value, the value that
it was before the 1. Override
Command was issued
ACK, no
action
1 - 4 0-10 3 Integer Read Binary
Output
Read Minimum On-time attribute
associated with each
individual point. Return value = 0
ACK, no
action
1 - 4 0-10 4 Integer Read Binary
Output
Read Minimum Off-time attribute
associated with each
individual point. Return value = 0
ACK, no
action
1 - 4 0-10 5 Integer Read Binary
Output
Read Maximum Cycles/ Hour attrib-
ute associated with each
individual point. Return value = 0
ACK, no
action
2 - 4 0-10 3 Integer Write Binary
Output
Write Minimum On-time attribute
associated with each individual
point
ACK, no
action
2 - 4 0-10 4 Integer Write Binary
Output
Write Minimum Off-time attribute
associated with each individual
point
ACK, no
action
2 - 4 0-10 5 Integer Write Binary
Output
Write Maximum Cycles/ Hour attrib-
ute associated with each
individual point
ACK, no
action
7 7 4 0-10 - - Write Binary
Output
Optional command for slave
devices. Only Attributes used for N2
commissioning purposes
ACK, no
action
7 8 4 0-10 - - Read Binary
Output
Optional command for slave
devices. Only Attributes used for N2
commissioning purposes
Instructions
VLT
®
Metasys
MG.11.G2.02 - VLT
®
is a registered Danfoss trademark 11
2 2