2.1.16 Internal Floating Point Commands (Acknowledged)
VLT
Response
Command Subcom-
mand
Region NPA Object no. Attribute No. Attribute Message Type Comments
ACK 1 - 5 0-101 1 Byte Read Internal
Parameter of
object type float
Read Object Status
associated with each
individual point
ACK 1 - 5 0-101 2 Float Read Internal
Parameter of
object type float
Read Current Value
attribute associated with
each individual point
ACK 2 - 5 0-101 - Float Write Internal
Parameter of
object type float
Write to Current Value
attribute associated with
each individual point
ACK 2 - 5 0-101 - Float Write Internal
Parameter of
object type float
Write to Current Value
attribute associated with
each individual point
ACK 7 2 5 0-101 - Float Override Internal
Parameter of
object type float
Write to internal parame-
ter current value (set-up
parameters for VLT)
ACK 7 3 5 0-101 - - Override Release Set the current value, the
value that it was before
the 1. Override
Command was issued
Instructions