2.2.2 Scaling of Bus Reference and Feedback
Reference/
feedback
Scaling Float IEEX hex
20% 20 * 16384/100 3276.8 454C CCCD
50% 50 * 16384/100 8192 4600 0000
100%
100 *
16384/100
16384 4680 0000
200%
200 *
16384/100
32767 46FF FE00
-100%
-100 *
16384/100
-16384 C680 0000
-200%
-200 *
16384/100
-32768 C700 0000
Table 2.1: Reference/feedback values
The reference/feedback value is the percentage of the range
of parameter 3-02 and 3-03. Values within the ranges 100% to
200% and -200% to -100% applies only to the reference. The
Float representation of the value 200% must be limited to
maximum 32767 and minimum -32768.
2.2.3
Status Update Request
A Status Update Request will cause the drive to report its
current operating status. The status codes, descriptions and
associated alarms are shown in the chart below.
The Device Status Code consists of two parts. The Least Signif-
icant Byte, (LSB) of the hex number is the Alarm Number. The
Most Significant Byte (MSB) indicates if the alarm is a normal
trip (01) that can be reset automatically or manually, or if the
alarm is a trip lock (02) requiring cycling power to the drive.
Status codes with associated alarms and descriptions
Device Status
Code1
Alarm
No.
Description
0x0000 - Device OK
0x0102 2 Live zero error
0x0204 4 Phase fault (Trip lock)
0x0107 7 Over voltage
0x0108 8 Under voltage
0x0109 9 Inverter overloaded
0x010A 10 Motor overloaded
0x010B 11 Motor thermistor
0x010C 12 Current limit
0x020D 13 Over current (Trip lock)
0x020E 14 Earth fault (Trip lock)
0x020F 15 Switch mode fault (Trip lock)
0x0210 16 Short circuit (Trip lock)
0x0111 17 Standard bus time out
0x0112 18 HPFB time out
0x0116 22 Auto optimization not OK
0x021D 29 Heat sink temperature to high (Trip
lock)
0x011E 30 Motor phase U missing
0x011F 31 Motor phase V missing
0x0120 32 Motor phase W missing
0x0122 34 Profibus communication error
0x0225 37 Inverter fault (Trip lock)
0x013C 60 Safety interlock
0x0263 99 Unknown fault (Trip lock)
Read/write notes
A write command to an ADF (Internal Floating Point) or BD
(Internal Byte) point type will be stored in the drive's EEPROM.
NOTE
If write command is issued to an overridden point, the
new value will not be stored in the drive's EEPROM.
Instructions
VLT
®
Metasys
MG.11.G2.02 - VLT
®
is a registered Danfoss trademark 15
2 2