Internal Integers (ADI), continued..
NPA Unit Description Range FC Par. Number
64 Sec Trip Delay on Overload 14-25
68 - PID Normal/Inverse 20-81
69 - PID Anti Windup 20-91
70 - Feedback 1 Conversion 20-01
71 - Feedback 1 Source Unit 20-02
72 - Feedback 2 Conversion 20-04
73 - Feedback 2 Source Unit 20-05
75 - Two Feedback Calculation 20-20
80 - Coasting 8-50
81 - DC Brake 8-52
82 - Start 8-53
83 - Reversing 8-54
84 - Selection of Setup 8-55
85 - Selection of Speed 8-56
90 - Reset kWh Counter 15-06
91 - Reset Running Hours Counter 15-07
92 - Operation Mode 14-22
101 -
Analogue Input, IO option X42/1
Mode
0 - 3 26-00
102 -
Analogue Input, IO option X42/3
Mode
0 - 3 26-01
103 -
Analogue Input, IO option X42/5
Mode
0 - 3 26-02
104 -
Analogue Input, GPIO option X30/8
Mode
6-60
105 -
Analogue Input, IO option X42/7
mode
0 -145 26-50
106 -
Analogue Input, IO option X42/9
Mode
0 -145 26-60
107 -
Analogue Input, IO option X42/11
Mode
0 -145 26-70
110 - ECB Bypass Mode 0 - 4 31-00
111 - ECB Bypass Start Timer Delay 0 - 60 31-01
112 - ECB Bypass Trip Bypass Delay 0 - 300 31-02
120 - Dry Pump Function 0 - 2 22-26
121 - Broken Belt Action 0 - 2 22-60
122 % Broken Belt Torque 0 - 100% 22-61
123 sec Broken Belt Timer 0 - 600 22-62
124 sec Interval Between Starts Par. 22-76 - 36-00 22-76
125 sec Minimum Run Time Par. 22-77 - 36-00 22-77
254 - Active Setup 0-10
Appendix
VLT
®
Metasys
28 MG.11.G2.02 - VLT
®