System design recommendations
Refrigerant charge limit Danfoss SM / SY / SZ compressors can tolerate 
liquid refrigerant up to a certain extend 
without major problems. However, excessive 
liquid refrigerant in the compressor is always 
unfavorable for service life. Besides, the 
installation cooling capacity may be reduced 
because of the evaporation taking place in the 
compressor and/or the suction line instead of the 
evaporator. System design must be such that the 
amount of liquid refrigerant in the compressor 
is limited. In this respect, follow the guidelines 
given in the section: “essential piping design 
recommendations” in priority.
Use the tables below to quickly evaluate the 
required compressor protection in relation with 
the system charge and the application. 
More detailed information can be found in the paragraphs hereafter. Please contact Danfoss 
Technical Support for any deviation from these guidelines. 
O-cycle migration O-cycle refrigerant migration is likely to occur 
when the compressor is located at the coldest 
part of the installation, when the system uses 
a bleed-type expansion device, or if liquid is 
allowed to migrate from the evaporator into 
the compressor sump by gravity. If too much 
liquid refrigerant accumulates in the sump it 
will saturate the oil and lead to a ooded start: 
when the compressor starts running again, 
the refrigerant evaporates abruptly under the 
sudden decrease of the bottom shell pressure, 
causing the oil to foam. In extreme situations, 
this might result in liquid slugging (liquid 
entering the scroll elements), which must be 
avoided as it causes irreversible damage to the 
compressor.
Danfoss SM/SZ/SY scroll compressors can 
tolerate occasional ooded starts as long as 
the total system charge does not exceed the 
maximum compressor refrigerant charge.
A suitable test to evaluate the risk of o-cycle 
migration is the following:
•  Stabilize the non running system at 41°F 
ambient temperature,
•  Raise the ambient temperature to 68°F and 
keep it for 10 minutes,
•  Start the compressor and monitor sump 
temperature, sight glass indication and sound 
level.
The presence of liquid in the crankcase can be 
easily detected by checking the sump level 
through the oil sight glass. Foam in the oil sump 
indicates a ooded start.
A noisy start, oil loss from the sump and sump 
cool down are indications for migration. 
Depending on the amount of migration graduate 
measures shall be taken:
•  Sump heater
•  Liquid line solenoid valve
•  Pump down cycle
REQREC
BELOW charge limit ABOVE charge limit
Cooling only systems, 
Packaged units
No test or additional safeties required
Refrigerant migration & oodback test 
Sump heater
Cooling only systems 
with remote condensor 
and split system units
Refrigerant migration & oodback test 
Crankcase heater, because full system 
charge is not denable (risk of overcharging)
Refrigerant migration & oodback test
Sump heater
Liquid receiver (in association with LLSV & pump down)
Reversible heat pump system
Specic tests for repetitive oodback
Sump heater
Defrost test   For more details refer to section "Reversible heat pump system.
Recommended   Required   No test or additional safeties required
Note: for special conditions such as low ambient temperature, low refrigerant load or brazed plate heat exchangers please refer 
to corresponding section "Specic application recommendations".
REC
REC
REQ
REQ
REQ
REQ
REQ
REQ
REQ
REC
Compressor models
Refrigerant charge limit 
(lbs)
S 084-090-100 19
S 110-120 22
S 112-124-147 17
S 148-161 28
S 175-185 30
S 240 35
S 300-380 44
33
FRCC.PC.003.A5.22
Application guidelines