Sump heaters
Sump heaters are strongly recommended on 
all systems where the compressor is exposed to 
low ambient temperatures, especially split and 
remote condenser installations. The sump heater 
will minimize refrigerant migration caused by 
the large temperature gradient between the 
compressor and the remainder of the system, 
please refer to section "O-cycle migration".
Specic application recommendations
Brazed plate heat 
exchangers
A brazed plate heat exchanger needs very little 
internal volume to satisfy the set of heat transfer 
requirements. Consequently, the heat exchanger 
oers very little internal volume for the 
compressor to draw vapor from on the suction 
side. The compressor can then quickly enter into 
a vacuum condition; it is therefore important 
that the expansion device be sized correctly 
and that a sucient pressure dierential across 
the expansion device be available to ensure 
adequate refrigerant feed into the evaporator. 
This aspect is of special concern when operating 
the unit under low ambient and load conditions. 
For further information on these conditions, 
please refer to the previous sections.
Due to the small volume of the brazed plate heat 
exchanger, no pump-down cycle is normally 
required. The suction line running from the heat 
exchanger to the compressor must be trapped to 
avoid refrigerant migration to the compressor.
When using a brazed plate heat exchanger as 
the condensing coil, a sucient free volume for 
the discharge gas to accumulate is required in 
order to avoid excess pressure buildup. At least 1 
meter of discharge line is necessary to generate 
this volume. To help reduce the gas volume 
immediately after start-up even further, the 
supply of cooling water to the heat exchanger 
may be opened before the compressor starts 
up so as to remove superheat and condense the 
incoming discharge gas more quickly.
Reversible heat pump 
systems
Transients are likely to occur in reversible heat 
pump systems, i.e. a changeover cycle from 
cooling to heating, defrost or low-load short 
cycles. These transient modes of operation 
may lead to liquid refrigerant carryover (or 
oodback) or excessively wet refrigerant return 
conditions. As such, reversible cycle applications 
require specic precautions for ensuring a long 
compressor life and satisfactory operating 
characteristics. Regardless of the refrigerant 
charge in the system, specic tests for repetitive 
oodback are required to conrm whether 
or not a suction accumulator needs to be 
installed. A crankcase heater and discharge gas 
thermostat are required for reversible heat pump 
applications.
The following considerations cover the most 
important issues when dealing with common 
applications. Each application design however 
should be thoroughly tested to ensure 
acceptable operating characteristics.
Electronic expansion valve The use of an electronic expansion valve requires 
a specic compressor start / stop control.
A specific compressor start sequence control has 
to be set when an electronic expansion valve 
(EXV) is used. The sequence must be adjusted 
according to the EXV step motor speed to allow 
time for the EXV to open before the compressor 
starts to avoid running under vacuum conditions.
The EXV should be closed at compressor stop 
not to let refrigerant in liquid phase entering the 
compressor. Ensure that the EXV closes when the 
supply voltage to the controller is interrupted (ie 
power cut o) by the use of a battery back up.
The compressors should be run for a 
minimum period in order to ensure that the 
oil has sucient time to properly return to the 
compressor sumps and that the motor has 
sucient time to cool under conditions of lowest 
refrigerant mass ows.
Low load operations
EXV Opened
 Closed
Compressor On
 O
37
FRCC.PC.003.A5.22
Application guidelines