Specic application recommendations
The use of a suction line accumulator is strongly 
recommended in reversible cycle applications as 
a result of the possibility of a substantial quantity 
of liquid refrigerant remaining in the evaporator, 
which acts as a condenser during the heating 
cycle. 
This liquid refrigerant can then return to the 
compressor, either ooding the sump with 
refrigerant or as a dynamic liquid slug when 
the cycle switches back to a defrost cycle or to 
normal cooling operations.
Sustained and repeated liquid slugging and 
oodback can seriously impair the oil’s ability 
to lubricate the compressor bearings. This 
situation can be observed in wet climates where 
it is necessary to frequently defrost the outdoor 
coil in an air source heat pump. In such cases a 
suction accumulator becomes mandatory.
Suction line accumulator
Apart from residual moisture in the system 
after commissioning, water could also enter the 
refrigeration circuit during operation. Water in 
the system shall always be avoided. Not only 
because it can shortly lead to electrical failure, 
sludge in sump and corrosion but in particular 
because it can cause serious safety risks. 
Common causes for water leaks are corrosion 
and freezing.
Corrosion: Materials in the system shall be 
compliant with water and protected against 
corrosion.
Freezing: When water freezes into ice its volume 
expands which can damage heat exchanger 
walls and cause leaks. During o periods water 
inside heat exchangers could start freezing when 
ambient temperature is lower than 32°F. During 
on periods ice banking could occur when the 
circuit is running continuously at too low load. 
Both situations should be avoided by connecting 
a pressure and thermostat switch in the safety 
line.
Water utilizing systems
39
FRCC.PC.003.A5.22
Application guidelines