Chapter 5 Function code VFD500 high performance vector control frequency inverter user manual
Static friction torque
compensation
0.00Hz~50.00Hz
It is used to overcome the static friction force at
the start, and the speed is higher than P14.11
and the static friction torque compensation is
cancelled.
0.0%~50.0%
Dynamic friction at rated speed
Notice: motor sliding friction torque at rated
rotating speed
Dynamic friction starting
value
Torque mode current
speed limit value (forward)
Display the current forward speed limit value,
unit: 0.01Hz
Torque mode current
speed limit value (reverse)
Display the current reverse speed limit value,
unit: 0.01Hz
16 Group Energy saving control
Electricity meter count
(32BIT)
Unit:0.1kw,output power will be negative in regen
state
Electricity meter zero
clearing
0:no function;1111:clear to zero
Energy saving voltage
limit
0%~50%(0% means Energy saving control
disable and more than 0% means Energy
saving control enable
Energy saving filter time
Notice:P16.05 is invisible(it is useful in vf control) and When energy
saving enabled, the output current can be reduced and thepower loss
can be reduced when the load is light.For example, the fan and pump is
light loaded, most of the inverters do not have this function, so we are
more energy efficient. Energy savings can be achieved when it is light
loads or load changes so slow