ALARM 250, New spare part
The power or switch mode power supply has been exchanged. The ad-
justable frequency drive type code must be restored in EEPROM. Select
the correct type code in par. 14-23
Typecode Setting
according to the
label on the unit. Remember to select ‘Save to EEPROM’ to complete.
ALARM 251, New type code
The adjustable frequency drive has a new type code.
7 Troubleshooting VLT AQUA High Power Instruction Manual
7-10
MG.20.P3.22 - VLT
®
is a registered Danfoss trademark
7