13-01 Start Event
Option: Function:
[5] Torque limit
[5] Torque limit The torque limit, set in
4-16 Torque Limit Motor Mode or
4-17 Torque Limit Generator Mode, has
been exceeded.
[6] Current limit
[6] Current limit The motor current limit,
set in 4-18 Current Limit, has been
exceeded.
[7] Out of current
range
[7] Out of current range The motor
current is outside the range set in
4-18 Current Limit.
[8] Below I low
[8] Below I low The motor current is
lower than set in 4-50 Warning Current
Low.
[9] Above I high
[9] Above I high The motor current is
higher than set in 4-51 Warning Current
High.
[10] Out of speed
range
[10] Out of speed range The speed is
outside the range set in 4-52 Warning
Speed Low and 4-53 Warning Speed
High.
[11] Below speed low
[11] Below speed low The output speed
is lower than the setting in
4-52 Warning Speed Low.
[12] Above speed
high
[12] Above speed high The output speed
is higher than the setting in
4-53 Warning Speed High.
[13] Out of feedb.
range
[13] Out of feedb. Range The feedback is
outside the range set in 4-56 Warning
Feedback Low and 4-57 Warning
Feedback High.
[14] Below feedb. low
[14] Below feedb. Low The feedback is
below the limit set in 4-56 Warning
Feedback Low.
[15] Above feedb.
high
[15] Above feedb. High The feedback is
above the limit set in 4-57 Warning
Feedback High.
[16] Thermal warning
[16] Thermal warning The thermal
warning turns on when the
temperature exceeds the limit in the
motor, the frequency converter, the
brake resistor or the thermistor.
[17] Mains out of
range
[17] Mains out of range The mains
voltage is outside the specified voltage
range.
[18] Reversing
[18] Reversing The output is high when
the frequency converter is running
counter clockwise (the logical product
of the status bits “running” AND
“reverse”).
13-01 Start Event
Option: Function:
[19] Warning
[19] Warning A warning is active.
[20] Alarm (trip)
[20] Alarm (trip) A (trip) alarm is active.
[21] Alarm (trip lock)
[21] Alarm (trip lock) A (Trip lock) alarm
is active.
[22] Comparator 0
[22] Comparator 0 Use the result of
comparator 0.
[23] Comparator 1
[23] Comparator 1 Use the result of
comparator 1.
[24] Comparator 2
[24] Comparator 2 Use the result of
comparator 2.
[25] Comparator 3
[25] Comparator 3 Use the result of
comparator 3.
[26] Logic rule 0
[26] Logic rule 0 Use the result of logic
rule 0.
[27] Logic rule 1
[27] Logic rule 1 Use the result of logic
rule 1.
[28] Logic rule 2
[28] Logic rule 2 Use the result of logic
rule 2.
[29] Logic rule 3
[29] Logic rule 3 Use the result of logic
rule 3.
[33] Digital input DI18
[33] Digital input DI18 Use the result of
digital input 18.
[34] Digital input DI19
[34] Digital input DI19 Use the result of
digital input 19.
[35] Digital input DI27
[35] Digital input DI27 Use the result of
digital input 27.
[36] Digital input DI29
[35] Digital input DI27 Use the result of
digital input 29.
[37] Digital input DI32
[37] Digital input DI32 Use the result of
digital input 32.
[38] Digital input DI33
[38] Digital input DI33 Use the result of
digital input 33.
[39] Start command
[39] Start command A start command is
issued.
[40] Drive stopped
[40] Drive stopped A stop command
( Jog, Stop, Qstop, Coast) is issued
and not from the SLC itself.
[41] Reset Trip
[41] Reset Trip A reset is issued
[42] Auto-reset Trip
[42] Auto-reset Trip An Auto reset is
performed.
[43] Ok key
[43] OK key The [OK] key is pressed.
[44] Reset key
[44] Reset key The [Reset] key is
pressed.
[45] Left key
[45] Left key The [] key is pressed.
[46] Right key
[46] Right key The [] key is pressed.
Parameter Descriptions