13-40 Logic Rule Boolean 1
Array [6]
Option: Function:
[73] SL Time-out 6
[74] SL Time-out 7
[75] Start command given
[76] Digital input x30/2
[77] Digital input x30/3
[78] Digital input x30/4
[79] Digital input x46/1
[80] Digital input x46/3
[81] Digital input x46/5
[82] Digital input x46/7
[83] Digital input x46/9
[84] Digital input x46/11
[85] Digital input x46/13
[90] ATEX ETR cur. warning
Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21]. If
the alarm 164 ATEX ETR
cur.lim.alarm is active, the output
will be 1.
[91] ATEX ETR cur. alarm
Selectable if1-90 Motor Thermal
Protection is set to [20] or [21]. If
the alarm 166 ATEX ETR
freq.lim.alarm is active, the output
will be 1.
[92] ATEX ETR freq. warning
Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21] ]. If
the alarm 163 ATEX ETR
cur.lim.warning is active, the
output will be 1.
[93] ATEX ETR freq. alarm
Selectable if 1-90 Motor Thermal
Protection is set to [20] or [21]. If
the warning 165 ATEX ETR
freq.lim.warning is active, the
output will be 1.
[94] RS Flipflop 0
[95] RS Flipflop 1
[96] RS Flipflop 2
[97] RS Flipflop 3
[98] RS Flipflop 4
[99] RS Flipflop 5
[100] RS Flipflop 6
[101] RS Flipflop 7
13-41 Logic Rule Operator 1
Array [6]
Option: Function:
Select the first logical operator to use on
the Boolean inputs from 13-40 Logic Rule
Boolean 1 and 13-42 Logic Rule Boolean 2.
[13-**] signifies the boolean input of
parameter group 13-**.
13-41 Logic Rule Operator 1
Array [6]
Option: Function:
[0] * DISABLED
Ignores 13-42 Logic Rule Boolean 2,
13-43 Logic Rule Operator 2, and 13-44 Logic
Rule Boolean 3.
[1] AND Evaluates the expression [13-40] AND
[13-42].
[2] OR Evaluates the expression [13-40] OR [13-42].
[3] AND NOT Evaluates the expression [13-40] AND NOT
[13-42].
[4] OR NOT Evaluates the expression [13-40] OR NOT
[13-42].
[5] NOT AND Evaluates the expression NOT [13-40] AND
[13-42].
[6] NOT OR Evaluates the expression NOT [13-40] OR
[13-42].
[7] NOT AND NOT Evaluates the expression NOT [13-40] AND
NOT [13-42].
[8] NOT OR NOT Evaluates the expression NOT [13-40] OR
NOT [13-42].
13-42 Logic Rule Boolean 2
Array [6]
Option: Function:
[0] * False Select the second boolean (TRUE
or FALSE) input for the selected
logic rule. See 13-01 Start Event
([0] - [61]) and 13-02 Stop Event
([70] - [75]) for further description.
[1] True
[2] Running
[3] In range
[4] On reference
[5] Torque limit
[6] Current limit
[7] Out of current range
[8] Below I low
[9] Above I high
[10] Out of speed range
[11] Below speed low
[12] Above speed high
[13] Out of feedb. range
[14] Below feedb. low
[15] Above feedb. high
[16] Thermal warning
[17] Mains out of range
[18] Reversing
[19] Warning
[20] Alarm (trip)
[21] Alarm (trip lock)
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark 123
3
3