16-85 FC Port CTW 1
Range: Function:
0 * [0 - 65535 ] View the two-byte Control word (CTW)
received from the Bus-Master. Interpretation of
the control word depends on the Fieldbus
option installed and the Control word profile
selected in 8-10 Control Profile.
16-86 FC Port REF 1
Range: Function:
0 * [-200 -
200 ]
View the two-byte Status word (STW) sent to
the Bus-Master. Interpretation of the Status
word depends on the fieldbus option installed
and the Control word profile selected in
8-10 Control Profile.
16-87 Bus Readout Alarm/Warning
Range: Function:
0 * [0 - 65535 ] Alarm and Warning numbers in hex as
displayed in the Alarm log. The High byte
contains the Alarm, the Low byte the Warning.
The Alarm number is the first one that
occurred after the last reset.
3.17.6 16-9* Diagnosis Read-Outs
16-90 Alarm Word
Range: Function:
0 * [0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code.
16-91 Alarm Word 2
Range: Function:
0 * [0 - 4294967295 ] View the alarm word sent via the serial
communication port in hex code.
16-92 Warning Word
Range: Function:
0 * [0 - 4294967295 ] View the warning word sent via the
serial communication port in hex code.
16-93 Warning Word 2
Range: Function:
0 * [0 - 4294967295 ] View the warning word sent via the
serial communication port in hex code.
16-94 Ext. Status Word
Range: Function:
0 * [0 - 4294967295 ] Returns the extended warning word sent
via the serial communication port in hex
code.
16-95 Ext. Status Word 2
Range: Function:
0 * [0 - 4294967295 ] Returns the extended warning word 2
sent via the serial communication port
in hex code.
16-96 Maintenance Word
Range: Function:
0
*
[0 -
4294967295 ]
Readout of the Preventive Maintenance
Word. The bits reflect the status for the
programmed Preventive Maintenance Events
in parameter group 23-1*. 13 bits represent
combinations of all the possible items:
Bit 0: Motor bearings
Bit 1: Pump bearings
Bit 2: Fan bearings
Bit 3: Valve
Bit 4: Pressure transmitter
Bit 5: Flow transmitter
Bit 6: Temperature transmitter
Bit 7: Pump seals
Bit 8: Fan belt
Bit 9: Filter
Bit 10: Drive cooling fan
Bit 11: Drive system health check
Bit 12: Warranty
Bit 13: Maintenance Text 0
Bit 14: Maintenance Text 1
Bit 15: Maintenance Text 2
Bit 16: Maintenance Text 3
Bit 17: Maintenance Text 4
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
148 MG33ME02 - VLT
®
is a registered Danfoss trademark
3