5-11 Terminal 19 Digital Input
Option: Function:
[10] * Reversing Functions are described under parameter group
5-1* Digital Inputs
5-12 Terminal 27 Digital Input
Option: Function:
[2] * Coast inverse Functions are described under parameter
group 5-1* Digital Inputs
5-13 Terminal 29 Digital Input
Option: Function:
Select the function from the available digital input
range and the additional options [60], [61], [63] and
[64]. Counters are used in Smart Logic Control
functions.This parameter is available for FC 302 only.
[14] * Jog Functions are described under parameter group 5-1*
Digital Inputs
5-14 Terminal 32 Digital Input
Option: Function:
Select the function from the available digital
input range.
[0] * No operation
Functions are described under 5-1* Digital
Inputs
5-15 Terminal 33 Digital Input
Option: Function:
Select the function from the available digital
input range and the additional options [60],
[61], [63] and [64]. Counters are used in
Smart Logic Control functions.
[0] * No operation
Functions are described under 5-1* Digital
Inputs
5-16 Terminal X30/2 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB101 is installed in the frequency
converter. Functions are described under
5-1* Digital Inputs
5-17 Terminal X30/3 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB101 is installed in the frequency
converter. Functions are described under
5-1* Digital Inputs
5-18 Terminal X30/4 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB101 is installed in the frequency
converter. Functions are described under
5-1* Digital Inputs
5-19 Terminal 37 Safe Stop
Option: Function:
[1]
*
Safe Stop
Alarm
Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital
input or fieldbus.
[3] Safe Stop
Warning
Coasts frequency converter when safe stop is
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset.
[4] PTC 1 Alarm Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital
input or fieldbus. Choice 4 is only available
when the MCB 112 PTC Thermistor Card is
connected.
[5] PTC 1
Warning
Coasts frequency converter when safe stop is
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset, unless a
Digital Input set to PTC Card 1 [80] is still
enabled. Choice 5 is only available when the
MCB 112 PTC Thermistor Card is connected.
[6] PTC 1 &
Relay A
This choice is used when the PTC option is
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency
converter when safe stop is activated. Manual
reset from LCP, digital input or fieldbus.
Choice 6 is only available when the MCB 112
PTC Thermistor Card is connected.
[7] PTC 1 &
Relay W
This choice is used when the PTC option is
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency
converter when safe stop is activated (T-37
off). When safe stop circuit is reestablished,
the frequency converter will continue without
manual reset, unless a Digital Input set to
PTC Card 1 [80] is (still) enabled. Choice 7 is
only available when the MCB 112 PTC
Thermistor Card is connected.
[8] PTC 1 &
Relay A/W
This choice makes it possible to use a
combination of Alarm and Warning. Choice 8
is only available when the MCB 112 PTC
Thermistor Card is connected.
[9] PTC 1 &
Relay W/A
This choice makes it possible to use a
combination of Alarm and Warning. Choice 9
is only available when the MCB 112 PTC
Thermistor Card is connected.
Choises 4 - 9 are only available when the MCB 112 PTC
Thermistor Card is connected.
Parameter Descriptions
VLT
®
AutomationDrive Programmming Guide
MG33ME02 - VLT
®
is a registered Danfoss trademark 75